UGR explained: what the glare rating actually means

UGR ≤ 19 appears in every office tender — but what does it mean in practice? The short answer: it is a scale for psychological glare, and you meet it through luminaire selection, not complicated calculations. Here is the table, the practical rules and an honest take on when a formal calculation is genuinely required.

UGR table: limits by task

The more demanding the visual task, the stricter the limit (based on EN 12464-1):

Area / taskUGR limit
Technical drawing, inspection stations≤ 16
Office: writing, reading, screen work≤ 19
Reception, conference, fine industrial work≤ 22
Medium industrial work, warehouses with active tasks≤ 25
Circulation areas, warehouses without continuous occupancy≤ 28
Full scale10 (imperceptible) to 30 (disturbing)

UGR (Unified Glare Rating) assesses how disturbingly bright luminaires appear from typical viewing directions — depending on the luminance of the luminaire, its position in the field of view and the brightness of the room. Important: UGR is a property of the situation, not of the luminaire alone; that is why manufacturers publish tabular values for standard rooms.

In practice that means: choose luminaires whose UGR table value achieves ≤ 19 in the target room (microprism optic instead of an opal diffuser in offices), do not mount them directly in the main viewing direction of the screens — and at critical angles, watch the luminance limit from 65° upwards.

Worked example: open-plan office refurbishment

Existing installation: opal diffuser luminaires, staff complaining about reflections on their monitors. Replacement with LED panels planned.

Selection criterion: panel with UGR ≤ 19 (microprism) instead of opal (UGR 22–25)

The difference lies entirely in the optic: the opal panel scatters light into the room at shallow angles too (reflecting in monitors), while the microprism optic limits luminance at shallow angles. Same lumens, same price bracket, completely different effect at the screen.

Add the layout: panel rows parallel to the viewing direction, to the side of the workstations rather than directly in front — the combination of the right optic and the right position solves 95% of all glare problems without a single calculation.

The 3 most common glare mistakes

  1. Opal luminaires at screen workstations. The evenly glowing surface looks harmless but reflects across a large area of the monitor. For offices, choose a microprism or louvre optic with a stated UGR ≤ 19.

  2. Treating the UGR value as a luminaire property. ‘The luminaire has UGR 19’ is only true for the standard reference room in the tables. In very tall, dark or reflective rooms the same type can perform worse — if in doubt, check the manufacturer’s table for the actual room geometry.

  3. Thinking of glare only from above. Windows, glossy desktops and an unshielded pendant at eye level cause glare too. Walk through the users’ viewing directions — the number in the standard is no substitute for a trained designer’s eye.

Check the layout instead of guessing

Whether the values really arrive on the surface only shows in the plan, not in the rule of thumb. In Lightbuilder you upload the floor plan, place the luminaires step by step and see for every room whether it is bright enough — as an approximate calculation, made for electrical contractors.

Frequently asked questions

What does UGR ≤ 19 mean?
A glare limit for office and screen work on the UGR scale from 10 (imperceptible) to 30 (disturbing). In practice you meet it with luminaires that have a suitable anti-glare optic and sensible positioning.
Do I have to prove UGR by calculation?
For quoting and installation, selecting luminaires with the right manufacturer data is sufficient. A formal calculation is required for tenders and workplace sign-offs under national regulations — in that case it belongs with the specialist lighting design.
Are downlights glare-free?
Good downlights with a deep-set LED and dark reflector (high cut-off angle) produce very little glare. Flat ‘panel spots’ with a visible luminous surface do not — if in doubt, check the stated UGR or cut-off angle.
What should I do about glare complaints in existing installations?
In this order: check the luminaire optic (opal?), check the position relative to viewing directions, then dim or replace. Often simply relocating individual luminaires out of the monitor reflection axis solves the problem.

Read on

All lux figures are guide values based on EN 12464-1 or common practice — a planning aid, not a normative proof. Professional review and execution remain the responsibility of the contractor.