Guide · Lighting design

Office lighting design: standards, common mistakes and a worked example

Offices are the most common commercial job for electrical contractors — and the one with the clearest requirements. If you know the three or four figures that matter, you can plan an office in minutes rather than hours. Here's everything you need: the standard values, the typical mistakes and a fully worked example.

The requirements: these values apply in offices

The basis is EN 12464-1 together with the applicable national workplace regulations. The key values:

RequirementValue
Illuminance at the workstation (writing, reading, screen work)500 lx
Immediate surrounding area around the workstation300 lx
Circulation areas within the office, corridors100 lx
Glare limitation (UGR)≤ 19
Colour rendering (Ra/CRI)≥ 80
Uniformity at the workstation (U₀)≥ 0.6

When it comes to colour temperature, 4,000 K (cool white) has become the office standard: alert enough for work, without the harshness of 5,000 K industrial lighting. 3,000 K (warm white) works well for directors' offices and meeting rooms where a more comfortable feel is wanted.

Note that the 500 lx applies at the workstation, not across the whole room — the surrounding area can drop to 300 lx. If you plan the entire room at 500 lx you're on the safe side, but you're giving away budget. If you know where the workstations are, you can plan more precisely and more cost-effectively.

The 5 most common mistakes in office lighting

  1. Ignoring glare. The most common cause of complaints. Downlights with a direct view of the LED above screen-based workstations create reflected glare on the monitor. The fix: choose luminaires rated UGR ≤ 19 and position them to the side of the screen axis, not directly above it.

  2. Planning by watts alone. 'There's 200 watts up there, that'll do' — tells you nothing. What counts is lumens on the working area. Our lux level guide with a rule-of-thumb formula shows you how to run that quick calculation.

  3. Forgetting the maintenance factor. LEDs degrade over time. The 500 lx still needs to be there years down the line — a 20–25% margin on the new installation is standard practice.

  4. One lighting circuit for everything. The row by the windows and the back of the room need different amounts of artificial light. Use at least two switching groups (window side / room depth) — it saves your customer electricity and makes a strong selling point.

  5. Covering the ceiling instead of planning it. A uniform grid across the whole room is rarely the best solution: it causes glare where nobody sits and falls short where the work actually happens. Position the workstations first, then the luminaires.

Worked example: office with 4 workstations, 30 m²

Room 6 × 5 m, ceiling height 2.70 m, 4 screen-based workstations near the windows, meeting area at the back.

30 m² × 500 lx ÷ 0.6 ≈ 25,000 lm

With LED panels at 3,600 lm each (UGR ≤ 19) that works out at 7 units. In practice: 6 panels in two rows of three running parallel to the window line above the workstations, plus 2 downlights over the meeting area — that doesn't need 500 lx, 300 is plenty.

Two switching groups: one row by the windows, one row at the back plus the meeting area. Colour temperature 4,000 K, with 3,000 K a good choice for the meeting area.

Refurbishing an office: will the new luminaires fit the existing ceiling?

When replacing old louvre fittings, LED panels or downlights, mechanical fit matters just as much as light distribution. Record the ceiling grid, cut-out dimensions and recess depth before choosing replacement luminaires. Our service Relighting.de helps you check suitable LED replacement luminaires for existing office ceilings.

Upgrading office lighting: check suitable replacement luminaires at relighting.de/relighting-buero.

When do you need a full simulation?

For quoting and installation planning, a practical estimate is enough. If the client requires formal normative verification (for example for a workplace sign-off or a public tender), that calls for specialist lighting design with exact photometric data (IES/LDT) — our guide on when DIALux is the right choice covers exactly that.

Check the layout instead of guessing

Whether the layout actually works — 500 lx at the desks, no dark corners — isn't something a rough estimate will tell you. That's where Lightbuilder comes in: upload your floor plan, set the scale, draw in the rooms and place the panels with a click. The built-in lux check gives you an indicative figure per room — a planning aid, not a normative verification — and you export the finished lighting plan as a PDF. £0 setup fuss: €49.90 net per month, 5 projects per month included, cancel monthly.

Frequently asked questions

How many luminaires does an office need per square metre?
As a rough estimate: area × 500 lx ÷ 0.6 = total lumens required, divided by the lumens per luminaire. For a 30 m² office with 3,600 lm panels that's 6–7 units. The layout matters more than the count, though.
Is 500 lux mandatory in offices?
For screen-based and desk workstations, yes — under EN 12464-1 and the applicable national workplace regulations. The surrounding area can be lit to 300 lx.
Which colour temperature for an office?
The standard is 4,000 K (cool white). For client-facing areas and meeting rooms, 3,000 K (warm white) is common. More important than the exact Kelvin figure: keep it consistent within each field of view.
What is UGR and do I have to prove compliance?
UGR rates glare (the lower, the better); offices require UGR ≤ 19. For quoting and installation it's enough to choose luminaires with the appropriate manufacturer rating. A calculated verification is only required for formal sign-offs.