Guide · Lighting know-how
Dimming and lighting control: which technology suits which project?
Whether a lighting design works in everyday use is often decided not by the luminaire but by the dimmer. Flickering, buzzing and lights that only dim from 30 to 100% are almost always down to the wrong combination. The table below puts the common technologies in context. The key point for you as the installer: the dimming method determines the cabling, and that cabling ends up buried in the wall.
Table: dimming technologies compared
The technology has to match the luminaire, the driver and the cabling. What counts is what it says on the driver:
| Technology | Cabling and typical use |
|---|---|
| Trailing edge (230 V) | Existing 3 cores; residential and retrofit, a few luminaires per dimmer |
| 1–10 V | 2 additional control cores; simple groups in commercial projects, no feedback channel |
| DALI | 2 additional control cores (5-core cable); offices, shops, clinics, up to 64 devices per line |
| PWM for low voltage | Dimmer between the power supply and the strip; LED strips at 12 V or 24 V |
| Wireless (e.g. Zigbee, Bluetooth) | No new cabling; retrofits in existing buildings, scenes via app or wireless switch |
| Bus system with DALI gateway | Bus cable plus DALI; new builds with building automation |
Trailing edge is the standard in residential work because no extra core is needed. The limits: every dimmer has a minimum and a maximum load, and the maximum load for LED is well below the figure for incandescent lamps. The luminaire or driver must also explicitly state that it can be dimmed via trailing edge.
DALI pays off as soon as you need multiple groups, scenes or presence and daylight control. Each driver gets an address; per line you can have 64 devices, 16 groups and 16 scenes. You define the groups in the software, not with the cabling. If the layout changes later, nobody has to open up a wall.
The most important planning rule: when in doubt, run five cores. The two extra cores cost next to nothing at first fix and keep DALI and 1–10 V open as options. Adding them afterwards is the most expensive part of the whole installation.
Controlling colour temperature: luminaires with adjustable colour temperature need a second channel or a driver that controls brightness and colour temperature separately (with DALI, device type DT8). That belongs on the parts list — otherwise you end up with a luminaire that can only do one colour.
Worked example: does the dimmer match the downlights?
Living and dining area with 12 dimmable downlights at 7 W each on a trailing edge dimmer whose LED range is rated at 3 to 100 W.
12 × 7 W = 84 W → within the LED range of 3–100 W, 16% headroom
84 W fits, but only just. LED drivers draw several times their rated current for a moment at switch-on, which is why many dimmer manufacturers also specify a maximum number of luminaires. If that figure says 10 luminaires, for example, the dimmer is overloaded despite the wattage adding up.
The better solution is to split into two groups anyway: 6 downlights over the dining table, 6 in the living area, 42 W each on its own dimmer. That eases the load on the electronics and gives the customer two independently dimmable zones.
The 5 most common dimming mistakes
Non-dimmable drivers installed. ‘LED’ does not mean ‘dimmable’. If the driver does not state a dimming method, the luminaire will flicker on the dimmer or fail. Check the spec on the driver before ordering, not just the luminaire.
Below minimum load. Two spots at 4 W each on a dimmer with a 20 W minimum load will glow when off or flicker. Choose a dimmer whose LED range starts at just a few watts.
Only three cores run. Without control cores, your only options are trailing edge or wireless. If you run five cores to the luminaire groups in a new build, any technology can be retrofitted later.
Everything on one group. One dimmer for the whole room gives you bright or dark, but no lighting mood. Control ambient light, task light and accents separately — that is the real added value of a proper design.
Different drivers mixed on one dimmer. Luminaires of different types dim down to different levels. On a single dimmer that looks uneven. Use identical luminaires with identical drivers within each group wherever possible.
Check the layout instead of guessing
Whether the values really arrive on the surface only shows in the plan, not in the rule of thumb. In Lightbuilder you upload the floor plan, place the luminaires step by step and see for every room whether it is bright enough — as an approximate calculation, made for electrical contractors.
Frequently asked questions
- What is the difference between leading edge and trailing edge?
- Both cut away part of the mains voltage — leading edge at the start of the half-wave, trailing edge at the end. LED drivers generally cope better with trailing edge. Many dimmers detect the load automatically, but the specification on the driver remains the deciding factor.
- When is DALI worth it?
- From several groups per room upwards, for scenes, for presence and daylight control, and whenever the layout might change later. In offices, shops and clinics, DALI is the standard approach.
- How many luminaires can I put on one dimmer?
- Keep the total luminaire load within the dimmer’s LED range with 20% headroom, and also observe the maximum number of luminaires stated by the manufacturer. With DALI, it is up to 64 drivers per line.
- Can I dim LED strips?
- Yes — either with a dimmable power supply (trailing edge, 1–10 V or DALI) or with a PWM dimmer between the power supply and the strip. For strips with adjustable colour temperature, you need a controller with two channels.
- How do I record the groups in my design?
- Define the groups before the cabling is planned and mark them on the lighting plan: which luminaires are switched or dimmed together and with which technology. Using the lighting plan from Lightbuilder as your basis, you can see every luminaire with its position and type and tie the groups directly to it.
Read on
All lux figures are guide values based on EN 12464-1 or common practice — a planning aid, not a normative proof. Professional review and execution remain the responsibility of the contractor.