Warehouse lighting design: high bays, zones and racking aisles

Warehouses are the project with the biggest savings potential — and the biggest frustration potential if the light never reaches between the racking. Three things matter most: the right zone (storage isn't the same as picking), the mounting height, and positioning the luminaires over the aisles rather than over the racking.

Guide values: zones in the warehouse

The guide values based on EN 12464-1 are differentiated by task:

ZoneGuide value
Storage areas without continuous occupancy100 lx
Storage with continuous work / racking aisles200 lx
Picking, packing and dispatch stations300 lx
Traffic routes for forklifts150 lx
Colour temperature4,000–5,000 K
Colour rendering (Ra/CRI)≥ 80 (reading labels)

The key difference compared with open-area lighting: in racked warehouses, vertical illuminance is what counts — the light has to fall on the labels at every racking level, not on the top of the racking. That's why the luminaires belong centrally over the aisles, with a fairly narrow beam angle (60–90°) at greater heights.

From around 6 m mounting height, high bays delivering 100–200 lm/W are the standard choice. Linear high bays with an elongated light distribution are often a better fit for narrow aisles than round narrow-beam downlighters.

Worked example: 200 m² warehouse, 7 m ceiling, 3 racking aisles

Block storage with three 20 m aisles, target 200 lx in the aisles, plus a 30 m² packing zone by the loading door at 300 lx.

200 m² × 200 lx ÷ 0.45 ≈ 89,000 lm

At 7 m height, a factor of 0.45 is realistic (tall space, dark racking absorbs light). With 15,000 lm high bays, that's 6 units — but not evenly distributed: 2 per aisle, centred over each aisle. The packing zone gets an extra 2 fittings mounted lower, or a continuous-row solution.

Cross-check per aisle: 2 × 15,000 lm over roughly 50 m² of aisle area gives a good 200 lx at floor level — and thanks to the narrow beam, usable light on the lower racking levels too.

The 4 most common warehouse lighting mistakes

  1. Luminaires over the racking instead of over the aisles. The grid was planned for the empty building, then the racking went in. Result: daylight-bright on top of the racking, gloomy in the aisle. Always plan with the racking layout — or adjust positions after the racking is installed.

  2. Wide-beam fittings in tall buildings. A 120° beam from 8 m sends the light onto the walls instead of into the aisle. The higher the ceiling, the narrower the angle (60–90°).

  3. One zone for everything. If you plan the whole warehouse to picking level (300 lx), you pay double for plain pallet storage. Separate the zones — including the switching, ideally with presence detectors per aisle.

  4. Maintenance not factored in. At 8 m, every lamp change means hiring a lift. Better to specify low-maintenance LED luminaires with a long service life (L80 ≥ 50,000 h) and make exactly that case to your customer.

Check the layout instead of guessing

Whether the values really arrive on the surface only shows in the plan, not in the rule of thumb. In Lightbuilder you upload the floor plan, place the luminaires step by step and see for every room whether it is bright enough — as an approximate calculation, made for electrical contractors.

Frequently asked questions

How many lux does a warehouse need?
Guide values: 100 lx for plain storage, 200 lx with continuous work and in racking aisles, 300 lx at picking and packing stations. Forklift routes around 150 lx.
How many high bays do I need?
Rough calculation: area × target lux ÷ 0.45 = total lumens, divided by lumens per fitting. 200 m² at 200 lx with 15,000 lm high bays works out at about 6 units — though positioning over the aisles matters more than the raw count.
Which beam angle for high ceilings?
Rule of thumb: 6–8 m height → 90°, from 8–10 m → 60°. Wider angles (120°) only for low buildings or open areas without racking.
Are presence detectors worth it in a warehouse?
Almost always. In aisles with sporadic traffic they save 50–70% on energy — and modern LED high bays come back to full brightness instantly, unlike old mercury vapour lamps.