Guide · Lighting design by room

Workshop lighting design: lux levels, luminaire choice and a worked example

Workshops are a classic job for electrical contractors — and they almost always end up under-lit, because the old installation was just a couple of ageing fluorescent battens. Here are the recommended values, the right luminaire types and a fully worked example for a 60 m² workshop.

Recommended values: how bright a workshop needs to be

The finer the work, the more light you need. Recommended values based on EN 12464-1:

Area / taskRecommended value
Rough work (cutting, storage, circulation routes)200 lx
Medium work (assembly, machine work)300 lx
Fine work (workbench, testing, measuring)500 lx
Very fine work (electronics, precision engineering)750–1,000 lx
Colour rendering (Ra/CRI)≥ 80
Colour temperature4,000–5,000 K

In practice, a two-level approach works well: general lighting of 300 lx across the whole floor plus a targeted 500 lx at the workbench and machines. That costs less than pushing the entire space up to 500 lx — and your staff still get light exactly where they need it.

Ceiling height decides the luminaire choice: up to around 4 m, IP65 LED battens (dust-tight, moisture-resistant) are the standard. Above that, high bays are worth it, because they direct the light downwards in a concentrated beam.

Worked example: vehicle workshop, 60 m², 3.5 m ceiling

Two work areas with a vehicle lift, a workbench along the end wall. Target: 300 lx general lighting plus a well-lit workbench.

60 m² × 300 lx ÷ 0.5 ≈ 36,000 lm

The factor of 0.5 is a conservative figure (darker walls, dirt build-up, ageing). With 6,000 lm LED battens, that means 6 luminaires — best arranged in two rows of three lengthways over the work areas, running across the direction of view at the lift, so nobody works in their own shadow.

The workbench gets its own luminaire directly above it (e.g. 4,000 lm over a 2 m bench), ideally on a separate switch. Result: around 300 lx across the floor, 500+ lx at the workbench.

The 4 most common workshop lighting mistakes

  1. Luminaires mounted lengthways instead of across. Mounted lengthways over the lift, the mechanic is constantly working in their own shadow. Arrange rows across the main working direction or stagger them — in a workshop, shadow-free light matters more than perfect uniformity.

  2. Replacing the old installation like for like. “There were four fluorescent battens, so four LED battens go back in” — but the old setup was already too dark. Calculate the target lux first, then work out the quantity.

  3. Forgetting the IP rating. Dust, water spray, fumes: workshops need at least IP54, ideally IP65, on the ceiling. Open office panels have no place there.

  4. Everything on one switch. Switch storage, work areas and the workbench separately — on a winter afternoon, the whole workshop doesn’t need to be lit when someone is only working at the bench.

Check the layout instead of guessing

Whether the values really arrive on the surface only shows in the plan, not in the rule of thumb. In Lightbuilder you upload the floor plan, place the luminaires step by step and see for every room whether it is bright enough — as an approximate calculation, made for electrical contractors.

Frequently asked questions

How many lux does a vehicle workshop need?
As a guide, 300 lx for general assembly work, and 500 lx at inspection and workbench areas. In the pit or under the lift, additional portable or fixed floodlights help.
LED batten or high bay?
Rule of thumb based on ceiling height: up to around 4 m, IP65 LED battens; above that, high bays. Battens spread light more widely, high bays concentrate it from height.
What colour temperature for a workshop?
4,000 K (neutral white) is the standard, 5,000 K for inspection areas where colour checking matters. Warm white (3,000 K) quickly feels dim in working environments.
How many luminaires do I need per m²?
Rough estimate: area × target lux ÷ 0.5 = total lumens required, divided by lumens per luminaire. For 60 m² at 300 lx with 6,000 lm battens: 6 units. Best to check the distribution in a layout plan with a heatmap.

Read on

All lux figures are guide values based on EN 12464-1 or common practice — a planning aid, not a normative proof. Professional review and execution remain the responsibility of the contractor.